Viessmann · Boiler troubleshooting

Replace gas valve

Vitocrossal 300 CA3B

What is going on

Install the new valve in the same orientation as the original. The gas pressure switches GDW1 and GDW2 are on the valve assembly.

Check in this order

  1. Disconnect the screws and connectors from the gas valve and both gas pressure switches.
  2. Pull the compensation line from the gas valve.
  3. Remove the nuts on the gas line flange and remove the flange.
  4. Remove the nuts on the Venturi flange and remove the flange.
  5. Install in reverse order, checking orientation.
  6. Replace the gaskets on the inlet and outlet sides.
  7. Secure the valve on the flange with screws, torque 13 lb.in (1.5 Nm), without stress on the flange.
  8. Do not interchange the connecting cables of GDW1 and GDW2.
  9. Check all fittings for gas tightness.
  10. Do not let leak detection spray touch electrical contacts.

Applies to: CA3B Series 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 60. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.