Riello · Boiler troubleshooting
Riello 40 F5 start-up settings on Ultra Oil boilers
What is going on
Starting settings from the Weil-McLain set-up chart. Final set-up must be done with a combustion analyzer.
Check in this order
- UO-3 at 0.80 GPH: Delavan 0.65 x 70B nozzle, 150 psi, turbulator 0, air gate 2.75.
- UO-3 at 1.00 GPH: 0.85 x 60B nozzle, 145 psi, turbulator 1, air gate 2.8.
- UO-4 at 1.20 GPH: 1.00 x 70B nozzle, 145 psi, turbulator 3, air gate 2.9.
- UO-5 at 1.40 GPH: 1.10 x 70B nozzle, 160 psi, turbulator 4, air gate 2.9.
- All 8 in. air tube, 4-1/4 in. insertion. End cone must sit at least 1/4 in. back from the inside face of the chamber refractory.
- Pump pressure range on this burner is 130 to 200 psig.
- Take final readings with the burner cover on. Readings change when the cover is off.
Applies to: Riello 40 F5 burner on Weil-McLain Ultra Oil UO-3, UO-4, UO-5
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Riello 40 F3/F5 oil burner installation & operating manual C6501071 (Weil-McLain Ultra Oil edition), Burner adjustment table p.12; Technical data p.2; Mounting p.4. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.