Riello 40 F5 start-up settings on Ultra Oil boilers

Riello 40 F5

What is going on

Starting settings from the Weil-McLain set-up chart. Final set-up must be done with a combustion analyzer.

Check in this order

  1. UO-3 at 0.80 GPH: Delavan 0.65 x 70B nozzle, 150 psi, turbulator 0, air gate 2.75.
  2. UO-3 at 1.00 GPH: 0.85 x 60B nozzle, 145 psi, turbulator 1, air gate 2.8.
  3. UO-4 at 1.20 GPH: 1.00 x 70B nozzle, 145 psi, turbulator 3, air gate 2.9.
  4. UO-5 at 1.40 GPH: 1.10 x 70B nozzle, 160 psi, turbulator 4, air gate 2.9.
  5. All 8 in. air tube, 4-1/4 in. insertion. End cone must sit at least 1/4 in. back from the inside face of the chamber refractory.
  6. Pump pressure range on this burner is 130 to 200 psig.
  7. Take final readings with the burner cover on. Readings change when the cover is off.

Applies to: Riello 40 F5 burner on Weil-McLain Ultra Oil UO-3, UO-4, UO-5

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Riello 40 F3/F5 oil burner installation & operating manual C6501071 (Weil-McLain Ultra Oil edition), Burner adjustment table p.12; Technical data p.2; Mounting p.4. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.