Riello 40 F5 will not run or air shutter will not close
What is going on
The electronic air shutter runs on 120 V. The burner motor will not start until the shutter is fully open.
Likely causes
- No constant 120 V on the AUX terminal of the sub-base
- Neutral and hot swapped
- Bad electronic air shutter
Check in this order
- Power off before opening the control box.
- Check for steady 120 V at the AUX terminal. Without it the burner will not run, or the shutter will not close after shutdown.
- Check that line and neutral are not reversed and the chassis is grounded.
- Check the safety limit and operating limit are separate and wired in series with the burner.
- If 120 V is there and the shutter does not move, replace the electronic air shutter (part 3020249; F5 replacement air damper kit C7001082).
Applies to: Riello 40 F5 burner on Weil-McLain Ultra Oil UO-3, UO-4, UO-5
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Riello 40 F3/F5 oil burner installation & operating manual C6501071 (Weil-McLain Ultra Oil edition), Internal factory wiring p.6; Application field wiring p.7; Setting the air adjustment plate p.11; Spare parts p.14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.