Riello · Boiler troubleshooting
Riello 40 burner in lockout (red lamp on)
What is going on
The 530 SE/C primary control locks out when it does not see flame after the oil valve opens. The lockout lamp is in the reset button.
Likely causes
- No oil to the nozzle (air in the pump, empty tank, plugged filter)
- Electrodes out of adjustment or bad ignition
- Dirty photocell
- Nozzle plugged or wrong
Check in this order
- Do not keep resetting. Each try sprays oil into the chamber. If oil has pooled in the chamber, clean it out before firing.
- Normal cycle motor and ignition start, about 12 s of pre-purge, then the oil valve opens. If no flame is seen, the control locks out a few seconds later (about 5 s on the start-up chart). Check the chart on p.12 for the exact timing.
- Check oil supply tank level, valves open, external filter clean.
- Purge air from the pump (see the pump purge guide).
- Power off. Pull the drawer assembly and check the electrode gaps (4 to 5 mm / 5/32 to 13/64 in.) and the nozzle.
- Check and clean the photocell.
- Reset once and watch a full cycle.
Applies to: Riello 40 F5 burner on Weil-McLain Ultra Oil UO-3, UO-4, UO-5
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Riello 40 F3/F5 oil burner installation & operating manual C6501071 (Weil-McLain Ultra Oil edition), Burner components p.2; Electrode setting p.8; Start-up cycle p.12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.