Riello · Boiler troubleshooting

Riello 40 burner in lockout (red lamp on)

Riello 40 F5

What is going on

The 530 SE/C primary control locks out when it does not see flame after the oil valve opens. The lockout lamp is in the reset button.

Likely causes

  • No oil to the nozzle (air in the pump, empty tank, plugged filter)
  • Electrodes out of adjustment or bad ignition
  • Dirty photocell
  • Nozzle plugged or wrong

Check in this order

  1. Do not keep resetting. Each try sprays oil into the chamber. If oil has pooled in the chamber, clean it out before firing.
  2. Normal cycle motor and ignition start, about 12 s of pre-purge, then the oil valve opens. If no flame is seen, the control locks out a few seconds later (about 5 s on the start-up chart). Check the chart on p.12 for the exact timing.
  3. Check oil supply tank level, valves open, external filter clean.
  4. Purge air from the pump (see the pump purge guide).
  5. Power off. Pull the drawer assembly and check the electrode gaps (4 to 5 mm / 5/32 to 13/64 in.) and the nozzle.
  6. Check and clean the photocell.
  7. Reset once and watch a full cycle.

Applies to: Riello 40 F5 burner on Weil-McLain Ultra Oil UO-3, UO-4, UO-5

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Riello 40 F3/F5 oil burner installation & operating manual C6501071 (Weil-McLain Ultra Oil edition), Burner components p.2; Electrode setting p.8; Start-up cycle p.12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.