Riello · Boiler troubleshooting
Purge air from the Riello 40 pump
What is going on
How to bleed the pump on gravity (one-pipe) and lift (two-pipe) systems.
Check in this order
- On a lift system, put a little oil into the vacuum port first to lubricate the pump gears.
- One-pipe, simple way open the bleeder until oil runs, close it and start the burner.
- One-pipe under pressure open the bleeder, disconnect the nozzle line at the pump nozzle port and run a plastic tube to a bucket. Start the burner holding the air tube cover in place. When the valve opens (about 10 s), lift the cover and shine a light on the photocell so it keeps running. When the oil is free of air, close the bleeder and shut the burner off right away. Reconnect the nozzle line and refit the cover.
- Never skip the step of disconnecting the nozzle line on a pressure bleed. Otherwise unburned oil collects in the chamber.
- Two-pipe power off, remove the air tube cover, shine a light on the photocell, power on and call for heat. The burner stays in pre-purge while the pump primes. When the hydraulic shutter opens, the pump is purged. Power off and refit the cover.
- Check all oil line joints for air leaks.
Applies to: Riello 40 F5 burner on Weil-McLain Ultra Oil UO-3, UO-4, UO-5
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Riello 40 F3/F5 oil burner installation & operating manual C6501071 (Weil-McLain Ultra Oil edition), Pump purge p.10-11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.