Riello 40 pump seal leaking or failed
What is going on
The pump shaft seal is easy to damage by the wrong oil line set-up.
Likely causes
- By-pass plug installed on a single-line (gravity) system
- Blocked or restricted return line on a two-line system
- Burner run before oil lines were connected
- NPT fittings forced into the pump's metric (British parallel) ports, or pipe dope / Teflon on pump connections
Check in this order
- Single-line system by-pass plug must NOT be in the pump. Two-line system: by-pass plug must be in the return port (use the 2.5 mm metric hex key).
- On two-line systems, check the return line is open, same size as the supply, and both reach the same depth in the tank.
- Use the supplied adapters on the pump ports. No pipe dope or Teflon tape on direct pump connections.
- Check suction lift height no more than 13 ft (4 m) and vacuum no more than 11.44 in. Hg. Check line lengths against the charts on p.9-10.
- Make sure an external oil filter is installed between tank and pump, and change it yearly.
Applies to: Riello 40 F5 burner on Weil-McLain Ultra Oil UO-3, UO-4, UO-5
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Riello 40 F3/F5 oil burner installation & operating manual C6501071 (Weil-McLain Ultra Oil edition), Oil line connections p.9-10. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.