Riello · Boiler troubleshooting

Riello 40 pump seal leaking or failed

Riello 40 F5

What is going on

The pump shaft seal is easy to damage by the wrong oil line set-up.

Likely causes

  • By-pass plug installed on a single-line (gravity) system
  • Blocked or restricted return line on a two-line system
  • Burner run before oil lines were connected
  • NPT fittings forced into the pump's metric (British parallel) ports, or pipe dope / Teflon on pump connections

Check in this order

  1. Single-line system by-pass plug must NOT be in the pump. Two-line system: by-pass plug must be in the return port (use the 2.5 mm metric hex key).
  2. On two-line systems, check the return line is open, same size as the supply, and both reach the same depth in the tank.
  3. Use the supplied adapters on the pump ports. No pipe dope or Teflon tape on direct pump connections.
  4. Check suction lift height no more than 13 ft (4 m) and vacuum no more than 11.44 in. Hg. Check line lengths against the charts on p.9-10.
  5. Make sure an external oil filter is installed between tank and pump, and change it yearly.

Applies to: Riello 40 F5 burner on Weil-McLain Ultra Oil UO-3, UO-4, UO-5

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Riello 40 F3/F5 oil burner installation & operating manual C6501071 (Weil-McLain Ultra Oil edition), Oil line connections p.9-10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.