Viessmann · Boiler troubleshooting
Checking the DHW tank, supply and room temperature sensors
What is going on
Test the NTC 10 kΩ sensors used for DHW tank, supply and room temperature. Measure across the plug terminals 1 and 2.
Likely causes
- Results very different from the curve point to the sensor or the lead
Check in this order
- Pull the sensor plug.
- Measure the resistance across plug terminals 1 and 2 and compare it with the curve.
- If the result is very different, disconnect the wires from the sensor and repeat the test on the sensor alone.
- Depending on the result, replace the lead or the sensor.
Applies to: DHW tank, supply and room sensors, Viessmann NTC 10 kΩ (blue)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 90. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.