Viessmann · Boiler troubleshooting

Checking the DHW tank, supply and room temperature sensors

Vitotronic 200Vitotronic 300-K

What is going on

Test the NTC 10 kΩ sensors used for DHW tank, supply and room temperature. Measure across the plug terminals 1 and 2.

Likely causes

  • Results very different from the curve point to the sensor or the lead

Check in this order

  1. Pull the sensor plug.
  2. Measure the resistance across plug terminals 1 and 2 and compare it with the curve.
  3. If the result is very different, disconnect the wires from the sensor and repeat the test on the sensor alone.
  4. Depending on the result, replace the lead or the sensor.

Applies to: DHW tank, supply and room sensors, Viessmann NTC 10 kΩ (blue)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 90. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.