Weil-McLain · Boiler troubleshooting

Check heat exchanger, vent seals and condensate dish joint for leaks

ECO Tec Series 3

What is going on

Find leaks at the top of the boiler using a mirror at high fire.

Likely causes

  • Loose retaining screws or nuts
  • Damaged gasket at a joint

Check in this order

  1. Run the boiler on high fire.
  2. Move an inspection mirror around all heat exchanger joints, vent connections and the condensate dish joints.
  3. A leak shows as vapor on the mirror; also look for weeping or other signs.
  4. If a leak is found, shut the boiler down immediately.
  5. Tighten the retaining screws or nuts without over-tightening.
  6. If still leaking, disassemble that joint, inspect the gasket and replace any damaged gasket.
  7. Contact WM Technologies Technical Services if the problem is not solved.

Applies to: ECO Tec Series 3 gas boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 136. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.