Cleaning boiler heating surfaces (annual)

CGi Series 5

What is going on

Annual cleaning of the heat exchanger sections, burners and base. Boiler contains ceramic fiber and fiberglass, so handle per the safety instructions in the manual.

Likely causes

  • Dust, lint and soot on the sections and burner ports
  • Sooting, which points to poor combustion

Check in this order

  1. Shut down the boiler using the To Turn Off Gas to Appliance instructions. Do not drain unless the boiler will be exposed to freezing; do not drain if antifreeze is in the system.
  2. Remove the venting connection to the boiler.
  3. Remove the top jacket panel and turn back the insulation.
  4. Remove the flue collector and clean the sealant from the assembly and sections.
  5. Remove the radiation plates hanging between sections.
  6. Remove the burners from the base. Brush and vacuum them and confirm all burner ports are clear.
  7. Place newspaper in the base to catch soot.
  8. Clean between sections with a wire flue brush.
  9. Remove the newspaper and soot. Vacuum or brush the base and surrounding area.
  10. Reinstall the radiation plates.
  11. Reinstall the collector box/transition and seal it so it is gas-tight to prevent flue gas spillage and CO.
  12. Reinstall insulation and the jacket top panel.
  13. Start up the boiler per the startup pages and the operating instructions.
  14. If sooting is found, check combustion and adjust as needed.

Applies to: CGi-25 to CGi-8

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 boiler manual, p. 72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.