Viessmann · Boiler troubleshooting

Verify burner input by clocking the gas meter

Vitodens 100-W, WB1B

What is going on

Check actual gas input by timing the meter with all other gas appliances on the same meter switched off. Do not overfire the boiler. Running 5% under-fired is acceptable.

Check in this order

  1. Turn off all other gas equipment served by the meter.
  2. Time how many seconds the boiler takes to use 10 cu. ft. of gas.
  3. Calculate input as (3600 x 10) divided by the seconds, then multiply by the gas heating value in Btu per cu. ft.
  4. Example 305 seconds and 1000 Btu/cu. ft. gives about 118,000 Btu/h for a 118,000 Btu/h boiler.
  5. Get the correct heating value from the gas utility before clocking the meter.

Applies to: Vitodens 100-W, WB1B, natural gas

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 100-W, WB1B installation and service instructions, p. 66. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.