Weil-McLain · Boiler troubleshooting
CGa boiler does not start (no fault shown)
What is going on
Quick checks before going into the fault table.
Likely causes
- Power off, blown fuse or loose connection
- Boiler set point below the water temperature
- Thermostat set below room temperature
- Gas off at the meter or boiler
- Inlet gas pressure too low
Check in this order
- Check the service switch, fuse and connections.
- Make sure the boiler temperature setting is above the current water temperature.
- Make sure the thermostat is calling (set above room temperature).
- Confirm gas is on at the meter and at the boiler.
- Gas work is for a gas-qualified tech only. Leak-test every fitting you open. Check inlet pressure: at least 5 in. w.c. on natural gas and 11 in. w.c. on propane.
- Still nothing check the display for a fault and use the fault table.
Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Start-up - If boiler doesn't start, p.54. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.