Weil-McLain · Boiler troubleshooting

CGa boiler does not start (no fault shown)

Weil-McLain CGa Series 4

What is going on

Quick checks before going into the fault table.

Likely causes

  • Power off, blown fuse or loose connection
  • Boiler set point below the water temperature
  • Thermostat set below room temperature
  • Gas off at the meter or boiler
  • Inlet gas pressure too low

Check in this order

  1. Check the service switch, fuse and connections.
  2. Make sure the boiler temperature setting is above the current water temperature.
  3. Make sure the thermostat is calling (set above room temperature).
  4. Confirm gas is on at the meter and at the boiler.
  5. Gas work is for a gas-qualified tech only. Leak-test every fitting you open. Check inlet pressure: at least 5 in. w.c. on natural gas and 11 in. w.c. on propane.
  6. Still nothing check the display for a fault and use the fault table.

Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Start-up - If boiler doesn't start, p.54. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.