Coco OT module overview and wiring

Versatronik 200

What is going on

The Coco OT module translates the Versatronik 200 CAN signal to OpenTherm for each OT-enabled boiler. Each boiler needs its own Coco OT module, and the control ships with two. Extra modules must be ordered for more than two OT boilers. Modules can be mounted near the control or near the boiler.

Check in this order

  1. Wire the Versatronik 200 to the Coco OT with 4-conductor cable (power and CAN).
  2. Wire the Coco OT to the boiler with 2-conductor cable (OpenTherm).
  3. Make sure CAN H and CAN L are not reversed, or communication faults can occur.
  4. Daisy-chain the modules from the previous Coco OT module.
  5. Plug the 4-pole connector into the Versatronik 200 only after all interconnections are complete.
  6. Set the DIP switches on each Coco OT for its boiler number (1 to 8).
  7. Check the boiler-specific manual for OT connections inside the boiler.

Applies to: Coco OT module with Versatronik 200 System Control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 installation and operating manual, p. 16-17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.