Display normal but hot water not hot enough
What is going on
Glow Brand C95/C140 shows normal on the display but the hot water is not hot enough. Usually it's a setpoint thing or the mixing valve. Scald risk is real above 120 F, so don't just crank it up.
Likely causes
- DHW setpoint set too low for the type of tank
- Thermostatic mixing valve set low or not working correctly
Check in this order
- Raise the DHW setpoint about 120 F with no tank, 120 to 140 F with a sensor tank (mode 1), 120 to 130 F with an aquastat tank (mode 2).
- Check the thermostatic mixing valve. Any setting over 120 F needs one installed.
- Confirm which mode the boiler is set for before changing the setpoint.
- Check delivered temperature at the tap with a thermometer, not by hand.
- Explain the scald risk to the homeowner after any increase.
Applies to: C95, C140 (NG and LP)
More boiler guides
Related
Glow Brand error codes · Glow Brand parts · Glow Brand tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Glow Brand C95 & C140 Installation & Operation Manual V.01282025 , Sec. 13.2 p.74. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.