System version 4: return temperature control with 3-way mixing valve
What is going on
Suited to older systems or where downstream heating circuits cannot be controlled. T1 closes the 3-way mixing valve in proportion when the minimum return temperature is not reached, which protects the boiler.
Check in this order
- Set coding 0C 1 for constant return temperature regulation.
- Set coding 4d 2 for the boiler circuit pump on plug sL.
- Connect T1 to plug aJA and set coding 4A 1.
- Size the boiler circuit pump for each boiler so its flow is at least the maximum total heating circuit flow. Recommended: 110%.
- Use field-supplied motor contactors or starters for single-phase and three-phase pumps.
Applies to: Vitorond 200 VD2, system version 4
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 15-16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.