Viessmann · Boiler troubleshooting

System version 4: return temperature control with 3-way mixing valve

Vitotronic 100 GC1Vitocontrol-S VD2/CT3/CM2

What is going on

Suited to older systems or where downstream heating circuits cannot be controlled. T1 closes the 3-way mixing valve in proportion when the minimum return temperature is not reached, which protects the boiler.

Check in this order

  1. Set coding 0C 1 for constant return temperature regulation.
  2. Set coding 4d 2 for the boiler circuit pump on plug sL.
  3. Connect T1 to plug aJA and set coding 4A 1.
  4. Size the boiler circuit pump for each boiler so its flow is at least the maximum total heating circuit flow. Recommended: 110%.
  5. Use field-supplied motor contactors or starters for single-phase and three-phase pumps.

Applies to: Vitorond 200 VD2, system version 4

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 15-16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.