Viessmann · Boiler troubleshooting

Top back panel screw relocation

Vitorond 100

What is going on

The top panel screw can be hard to remove. Move it about 3 in to the left or right and drill a new pilot hole. The source text for the drill bit size is garbled on the Vitotronic version, so confirm the size before drilling.

Check in this order

  1. Remove the top panel screw, or move it about 3 in left or right.
  2. Pre-drill the new mounting hole with a 1/8 in drill bit through the top back panel and into the back panel.
  3. Reinstall the screw in the new hole.

Applies to: Vitorond 100 VR1 40 to 63, 161 to 245

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 100 VR1 installation and service instructions, p. 21 and p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.