Navien · Boiler troubleshooting

Condensate drain piping

NCB700

What is going on

Route the condensate line from the boiler's 1/2 in NPT drain fitting at the bottom of the unit. Use only corrosion-resistant pipe such as PVC or CPVC, and do not reduce the fitting or line below 1/2 in. The boiler must sit higher than the top of the drain point. The drain line needs a negative slope. Where a condensate pump is used, it must handle at least 2 gallons per hour for each boiler on the system.

Check in this order

  1. Choose a drain option direct to an external drain, to an external drain through a neutralizer, or from the boiler to a pump and then to the drain.
  2. Connect a 1/2 in corrosion-resistant drain line to the bottom fitting and run it to a suitable drain.
  3. If no pump is used, slope the line down at least 1/4 in per foot.
  4. If a pump is used, confirm it moves at least 2 gal/hr per boiler.
  5. Fill the condensate trap by pouring water into the flue outlet until water runs out of the condensate drain.
  6. Keep the line from freezing and from blocking, or condensate can leak from the drain.

Applies to: NCB700 condensate drain

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 192-193. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.