Navien · Boiler troubleshooting
Condensate drain piping
What is going on
Route the condensate line from the boiler's 1/2 in NPT drain fitting at the bottom of the unit. Use only corrosion-resistant pipe such as PVC or CPVC, and do not reduce the fitting or line below 1/2 in. The boiler must sit higher than the top of the drain point. The drain line needs a negative slope. Where a condensate pump is used, it must handle at least 2 gallons per hour for each boiler on the system.
Check in this order
- Choose a drain option direct to an external drain, to an external drain through a neutralizer, or from the boiler to a pump and then to the drain.
- Connect a 1/2 in corrosion-resistant drain line to the bottom fitting and run it to a suitable drain.
- If no pump is used, slope the line down at least 1/4 in per foot.
- If a pump is used, confirm it moves at least 2 gal/hr per boiler.
- Fill the condensate trap by pouring water into the flue outlet until water runs out of the condensate drain.
- Keep the line from freezing and from blocking, or condensate can leak from the drain.
Applies to: NCB700 condensate drain
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 192-193. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.