Weil-McLain · Boiler troubleshooting
Check boiler relief valve
What is going on
Verify the relief valve is clear and seats properly.
Likely causes
- Mineral deposits on the valve
- Expansion tank waterlogged or undersized
- Valve not seating
Check in this order
- Make sure a discharge line is piped to a safe place before operating the lever.
- Lift the lever to confirm water flow. If no water flows, the valve is inoperative and the boiler must be shut down until a new valve is installed.
- Operate the lever at least once a year.
- If the valve weeps or will not seat, replace it.
- Confirm the weeping is from the valve and not system over-pressurization from expansion tank problems.
- Relief valves must be reinspected at least once every three years by a licensed plumbing contractor or authorized inspection agency.
Applies to: ECO Tec Series 3 boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 144. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.