Check boiler relief valve

ECO Tec Series 3

What is going on

Verify the relief valve is clear and seats properly.

Likely causes

  • Mineral deposits on the valve
  • Expansion tank waterlogged or undersized
  • Valve not seating

Check in this order

  1. Make sure a discharge line is piped to a safe place before operating the lever.
  2. Lift the lever to confirm water flow. If no water flows, the valve is inoperative and the boiler must be shut down until a new valve is installed.
  3. Operate the lever at least once a year.
  4. If the valve weeps or will not seat, replace it.
  5. Confirm the weeping is from the valve and not system over-pressurization from expansion tank problems.
  6. Relief valves must be reinspected at least once every three years by a licensed plumbing contractor or authorized inspection agency.

Applies to: ECO Tec Series 3 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 144. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.