Viessmann · Boiler troubleshooting
External changeover between staged and modulating burner
What is going on
A dry contact on plug aVH switches the burner between two-stage and modulating operation.
Check in this order
- Connect a dry contact to terminals 1 and 2 of plug aVH.
- Contact open modulating operation.
- Contact closed two-stage operation.
- Set the burner type to modulating in coding 1 (coding "02: 2").
Applies to: Staged/modulating burner changeover
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 51. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.