SVF cascade: member boiler stops when it loses the master
What is going on
In a cascade, a member boiler shuts down when it loses communication with the master unless it was set up to keep running. The wizard default is No.
Likely causes
- Boiler-to-boiler communication cable loose, damaged or wired wrong
- Master boiler off or its control down
- Member set to not run on lost communication
Check in this order
- Check the master boiler is powered and running.
- Check the boiler-to-boiler communication cables (Section 3 wiring, p.67 / p.80).
- If the building needs heat even when the link is lost, set the member's "run if communication is lost" answer to Yes. It will then hold a fixed setpoint or the last setpoint from the master, whichever is chosen.
Applies to: SVF 725, 850, 1000 (Series 1) and SVF 1500-3000 (Series 2)
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF 725/850, 1000 Series 1 / 1500-3000 Series 2 Advanced Installation Manual 550-143-071/0924, Express Setup Multi-Boilers notes, p.22-23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.