Viessmann · Boiler troubleshooting
Install and connect the outdoor temperature sensor
What is going on
Mount and wire the outdoor sensor so it reads outdoor air correctly and is kept away from line voltage.
Check in this order
- Remove the cover of the outdoor temperature sensor.
- Mount the wall-mount base with the cable entry pointing downward.
- Route the cable from the boiler control board to the outdoor sensor and connect it to the sensor terminals (wires are interchangeable).
- Connect the outdoor sensor to terminals X3.1/X3.2 on the boiler control board (wires are interchangeable).
- Place the cover on the base and snap it into place.
- Use 2-wire cable, max 95 ft (35 m), minimum AWG 16 copper.
- Mount the sensor 6.6 to 8.2 ft (2 to 2.5 m) above ground on the north or northwest wall. In a multi-storey building, mount it in the upper half of the second floor.
- Do not mount the sensor above windows, doors or air vents, or directly under a balcony or gutter.
- Do not cover the sensor with plaster. If the wall is not yet plastered, allow for the plaster thickness or remove the sensor before plastering.
- Do not route the sensor cable near line voltage wiring (120/240 V).
Applies to: Models 45, 57, 160, 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB installation instructions, p. 50. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.