Viessmann · Boiler troubleshooting
Gas train components (NG and LPG)
What is going on
The gas train includes a manual shut-off valve for each fuel, a combination gas valve assembly, a low and a high gas pressure switch, a fan pressure switch, a test fire valve, a Venturi, and separate solenoid valves for NG and LPG. A gas changeover valve selects the fuel. Each burner control requires a manual reset after a low gas pressure condition. Burner sections are lead (section 1), lag 1 (section 2) and, on 5.0 and 6.0 models, lag 2 (section 3). The gas train meets ASME/CSD-1.
Check in this order
- Reset the burner control manually after a low gas pressure event.
- Verify the fuel changeover valve and the matching solenoid are set for the fuel in use.
Applies to: Vitocrossal 300 CA3 and CA3B models 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocrossal 300 CA3B Dual Fuel installation manual, p. 41, 43. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.