Viessmann · Boiler troubleshooting

Mounting the Vitocontrol-S control unit

Vitocontrol-S VD2/CT3/CM2

What is going on

Wall mounting sequence for the control unit, connection enclosure and midplate on the metal backplate.

Check in this order

  1. Fasten the metal backplate to the mounting surface with four fasteners.
  2. Position the midplate between the backplate and the connection enclosure.
  3. Install the midplate and connection enclosure onto the backplate.
  4. Fasten the connection enclosure and midplate to the backplate with two fasteners.
  5. Install the control rear section onto the connection enclosure housing, hook it onto the backplate tabs and pivot it downwards.
  6. Fasten the control rear section to the connection enclosure with two fasteners.

Applies to: Vitocontrol-S VD2/CT3/CM2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation manual, p. 75. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.