Steam boiler water level and start-up checks

EGPEG

What is going on

Water level must be checked before start-up. Steam water level should be no more than half way up the gauge glass and not less than 1/4 in. above the bottom of the glass; approximately half way up is typical.

Check in this order

  1. Verify water level is no more than half of the gauge glass and at least 1/4 in. above the bottom of the glass.
  2. Verify the preparation procedures on the previous pages are complete.
  3. Check boiler water level; it should be about half way up the gauge glass.
  4. Remove the boiler jacket door and note the gas valve manufacturer and model number.
  5. Use the operating instructions that apply to that gas valve (Table 14, page 58).
  6. Follow the operating instructions to start the boiler.
  7. If the boiler fails to start, check loose connections, blown fuse or service switch, high limit set below boiler pressure, thermostat set below room temperature, gas off, and incoming gas pressure below 5 in. w.c.

Applies to: EG / PEG steam boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG / PEG Series 7 boiler manual, p. 62-63. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.