Navien · Boiler troubleshooting

Relief valve discharging - Navien NHB-H / NFB-H

What is going on

The pressure relief valve drips or discharges, or pressure climbs high when the boiler heats.

Likely causes

  • Expansion tank waterlogged, undersized or isolated
  • Make-up / pressure reducing valve over-filling
  • Relief valve rating too low for the system pressure (NFB-H)

Check in this order

  1. Do not plug or cap the relief valve.
  2. Watch system pressure as the boiler heats; a large rise points to the expansion tank.
  3. Check the expansion tank pre-charge and size, and that it is on the pump suction side and cannot be isolated.
  4. Check the make-up water valve is not raising pressure above the fill setting (typical 12 psi).
  5. NHB-H system 12-30 psi with a 30 psi valve. NFB-H: 12-80 psi; if a higher-rated ASME valve (up to 80 psi) is fitted, set parameter 17 High Sys Pressure to suit.
  6. Replace the relief valve if it leaks after pressure is correct.

Applies to: Navien NHB-H and NFB-H condensing boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NHB-H Installation and Operation Manual, 3.1.2 p.17-19 and 3.5 p.28; NFB-H Installation Manual 3.1.2 p.19-21, 11.6.3 p.109; NHB-H User's Information Manual p.20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.