Viessmann · Boiler troubleshooting

Combustion fault: pulsation

Vitocrossal 300 CA3B

What is going on

Burner pulsates during operation with no fault code shown.

Likely causes

  • Excessive gas input
  • Insufficient or excessive air
  • Condensate build-up in flue system
  • Incorrect flue outlet

Check in this order

  1. Adjust gas input to match the rated boiler heating output.
  2. Check the condensate drain.
  3. Check the flue outlet and flue system.

Applies to: CA3B Series 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B service instructions, p. 31. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.