Circulator zoning with primary/secondary piping

SlimFit Series 3

What is going on

Each zone has its own circulator and the boiler loop runs as a secondary off the primary system loop. Optional DHW piping can be added.

Check in this order

  1. Install a separate circulator for each zone, sized for the flow and head needed.
  2. Fit a flow/check valve on the boiler outlet to stop gravity circulation during DHW heating.
  3. Pipe the boiler loop at least to the minimum size in Figure 4 (p. 13).
  4. Provide an expansion tank per p. 14. No closed-type tank if the DHW heater has an automatic vent.
  5. For a DHW tank wired as a zone, the tank must not already be connected to the boiler. Set the Advanced Manual parameters so the boiler circulator runs on DHW calls and TARGET MOD SENSOR is System Supply.
  6. Choose a DHW priority scheme DHW priority, space heating priority, or no priorities (only when DHW is a zone; do not use outdoor reset in that case).
  7. The boiler circulator cannot be used as a zone pump. For more than 3 zones, use the WMCR zone circulator controller.

Applies to: SF-550 and SF-750

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 3 boiler manual 550-100-559/0725, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.