Circulator zoning with primary/secondary piping
What is going on
Each zone has its own circulator and the boiler loop runs as a secondary off the primary system loop. Optional DHW piping can be added.
Check in this order
- Install a separate circulator for each zone, sized for the flow and head needed.
- Fit a flow/check valve on the boiler outlet to stop gravity circulation during DHW heating.
- Pipe the boiler loop at least to the minimum size in Figure 4 (p. 13).
- Provide an expansion tank per p. 14. No closed-type tank if the DHW heater has an automatic vent.
- For a DHW tank wired as a zone, the tank must not already be connected to the boiler. Set the Advanced Manual parameters so the boiler circulator runs on DHW calls and TARGET MOD SENSOR is System Supply.
- Choose a DHW priority scheme DHW priority, space heating priority, or no priorities (only when DHW is a zone; do not use outdoor reset in that case).
- The boiler circulator cannot be used as a zone pump. For more than 3 zones, use the WMCR zone circulator controller.
Applies to: SF-550 and SF-750
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 3 boiler manual 550-100-559/0725, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.