Weil-McLain · Boiler troubleshooting
Metal flakes in vent outlet or vent (flueway corrosion)
What is going on
Metal flakes indicate contaminated combustion air or condensation of flue gases inside the boiler sections.
Likely causes
- Contaminated combustion air supply
- Condensation of combustion gases in boiler sections from poorly regulated return water temperature
Check in this order
- Remove any contaminating products from the combustion air area (see page 5 of the manual)
- Provide outside air for combustion
- Have a qualified service technician inspect system piping and controls to confirm return water temperature is properly regulated
Applies to: All listed CGa, CGi, EG, PEG and LGB boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain CGa, CGi, EG, PEG & LGB user manual, p. 9. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.