Weil-McLain · Boiler troubleshooting

Fill and test the water system

SVF Series 1

What is going on

Fill only after the water meets the chemistry limits. Check for leaks at fill and during startup.

Check in this order

  1. Close manual and automatic air vents and the boiler drain valve.
  2. Fill to the correct system pressure. Pressure rises when the boiler heats up.
  3. Keep operating pressure at or below 80% of the relief valve setting for most systems.
  4. Check the whole system for leaks at fill and during startup, and repair all leaks before going on.
  5. Add Sentinel X100 inhibitor after filling, following the container directions, then recheck the level and add more if needed.

Applies to: SVF 1500, 2000, 2500, 3000

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 85. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.