Weil-McLain · Boiler troubleshooting
Zone valve zoning with high-flow DHW circuit (primary/secondary)
What is going on
Use when the DHW circuit needs more flow than the boiler allows, or with a high pressure-drop coil-type DHW tank. DHW flows only through the secondary connection piping, which keeps the boiler circulator head off the zone valves.
Check in this order
- Size the primary/secondary connection piping (Fig. 8, item 23) for the full flow it must carry.
- Install a system circulator sized for the required flow and head.
- Fit a flow/check valve on the boiler outlet to stop gravity circulation during DHW heating.
- Pipe all boiler loop runs at least to the minimum pipe size in Figure 4 (p. 13).
- Provide a system expansion tank per p. 14. Do not use a closed-type tank if the DHW heater has an automatic vent.
- Set DHW and space heating priorities DHW on Priority 1 with space heating on 2 and/or 3, or space heating on 1 and/or 2 with DHW on 3. The control never runs two priorities at once.
- For more than 3 zones, use the WMZV zone valve controller.
Applies to: SF-550 and SF-750
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 3 boiler manual 550-100-559/0725, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.