Zone valve zoning with high-flow DHW circuit (primary/secondary)

SlimFit Series 3

What is going on

Use when the DHW circuit needs more flow than the boiler allows, or with a high pressure-drop coil-type DHW tank. DHW flows only through the secondary connection piping, which keeps the boiler circulator head off the zone valves.

Check in this order

  1. Size the primary/secondary connection piping (Fig. 8, item 23) for the full flow it must carry.
  2. Install a system circulator sized for the required flow and head.
  3. Fit a flow/check valve on the boiler outlet to stop gravity circulation during DHW heating.
  4. Pipe all boiler loop runs at least to the minimum pipe size in Figure 4 (p. 13).
  5. Provide a system expansion tank per p. 14. Do not use a closed-type tank if the DHW heater has an automatic vent.
  6. Set DHW and space heating priorities DHW on Priority 1 with space heating on 2 and/or 3, or space heating on 1 and/or 2 with DHW on 3. The control never runs two priorities at once.
  7. For more than 3 zones, use the WMZV zone valve controller.

Applies to: SF-550 and SF-750

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 3 boiler manual 550-100-559/0725, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.