Viessmann · Boiler troubleshooting

Piping for heating and cooling applications

Vitorond 200 VD2

What is going on

When the boiler is used with a chiller or cooling coils in air handlers, the piping must keep chilled water out of the boiler.

Likely causes

  • Chilled water entering the boiler
  • Gravity circulation of boiler water during the cooling cycle

Check in this order

  1. Pipe the chilled medium in parallel with the boiler and install valves to keep chilled medium out of the boiler.
  2. On systems with heating coils in air handlers exposed to refrigerated air, install flow control valves or another automatic means to stop gravity circulation during cooling.
  3. At the start of cooling season, close valve V1 and open valve V2.
  4. At the start of heating season, close valve V2 and open valve V1.
  5. Attach a metal tag to these valves stating their purpose.
  6. Run the circulating pump from its own on/off switch, not from the boiler pump aquastat.
  7. Check the chiller manufacturer's installation instructions for further requirements.

Applies to: VD2-320 to VD2-1080

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2 installation manual, p. 38. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.