Piping for heating and cooling applications
What is going on
When the boiler is used with a chiller or cooling coils in air handlers, the piping must keep chilled water out of the boiler.
Likely causes
- Chilled water entering the boiler
- Gravity circulation of boiler water during the cooling cycle
Check in this order
- Pipe the chilled medium in parallel with the boiler and install valves to keep chilled medium out of the boiler.
- On systems with heating coils in air handlers exposed to refrigerated air, install flow control valves or another automatic means to stop gravity circulation during cooling.
- At the start of cooling season, close valve V1 and open valve V2.
- At the start of heating season, close valve V2 and open valve V1.
- Attach a metal tag to these valves stating their purpose.
- Run the circulating pump from its own on/off switch, not from the boiler pump aquastat.
- Check the chiller manufacturer's installation instructions for further requirements.
Applies to: VD2-320 to VD2-1080
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2 installation manual, p. 38. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.