Navien · Boiler troubleshooting

Reach gateway in local browser by changing PC subnet (Windows 10)

Modbus/BACnet Gateway

What is going on

Give the PC a static address on the gateway's default 192.168.1.xxx subnet. Use only one access method, either this or the FieldServer Toolbox.

Likely causes

  • PC and gateway on different IP networks

Check in this order

  1. Open Control Panel, then Network and Internet, then Network and Sharing Center.
  2. Select Change adapter settings.
  3. Right-click Local area Connection and select Properties.
  4. Highlight Internet Protocol Version 4 and click Properties.
  5. Enter a static IP on the same subnet as the gateway, for example 192.168.1.xxx with mask 255.255.255.0.
  6. Click OK, then Close to finish.

Applies to: Windows 10 PC with gateway at default 192.168.1.24

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien Modbus/BACnet gateway installation and operation manual, p. 10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.