Run a participant check on the LON network
What is going on
Confirms that a participant on the LON network answers from the boiler control side. Use it to verify communication after addressing.
Check in this order
- Make sure the Vitotronic 300-K is coded as error manager and each gateway has a unique participant number from the rotary dial.
- Press OK and Menu together for about 2 seconds to open the Service screen.
- Arrow down to Service Functions and select it.
- Select Participant Check if not already highlighted and press OK.
- Arrow up or down to pick a participant and press OK. The screen shows whether the check is active and reports if it passed.
- If it passed, pick another participant with the arrow keys, press OK and repeat.
- Press the return button to exit the participant check.
- If a participant should not be in the list, or the gateway address has changed, select Delete List? to remove it. This also clears the related communication fault.
Applies to: Versatronik 501 gateways on Viessmann controls
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 501 NR2/LON communication manual, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.