Viessmann · Boiler troubleshooting
Rooms cold during the day but warm at night
What is going on
The heating timing does not match the day and night pattern.
Likely causes
- Time incorrectly set
- Control unit incorrectly programmed or set
Check in this order
- Set the correct time.
- Check and correct the temperature, time program and heating program settings.
Applies to: Vitocontrol-S VD2/CT3/CM2
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 35. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.