Weil-McLain · Boiler troubleshooting

Check control module and circulator/blower fuses

SVF Series 1

What is going on

Check fuses before replacing the control module or major components such as the blower. A blown fuse can keep the control or components from running.

Likely causes

  • Blown control, circulator or blower fuse

Check in this order

  1. Turn off power at the external line switch.
  2. Remove the top front slate panel, slide the glossy black panel up, remove the middle slate panel (two screws), and remove the control box cover (three screws).
  3. Remove and inspect the two control fuses and the expansion module fuse.
  4. Replace any blown fuse with the specified type and rating only. Never jumper a fuse.
  5. Inspect the boiler circulator and blower fuses and replace any blown fuse with the specified rating.
  6. Reinstall the control box cover (three screws), middle panel (two screws), glossy black panel and top slate panel.
  7. Restore power at the external line switch and verify operation.

Applies to: SVF 1500-3000 Series 1 boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF Series 1 boiler manual, p. 100. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.