Weil-McLain · Boiler troubleshooting
Check control module and circulator/blower fuses
What is going on
Check fuses before replacing the control module or major components such as the blower. A blown fuse can keep the control or components from running.
Likely causes
- Blown control, circulator or blower fuse
Check in this order
- Turn off power at the external line switch.
- Remove the top front slate panel, slide the glossy black panel up, remove the middle slate panel (two screws), and remove the control box cover (three screws).
- Remove and inspect the two control fuses and the expansion module fuse.
- Replace any blown fuse with the specified type and rating only. Never jumper a fuse.
- Inspect the boiler circulator and blower fuses and replace any blown fuse with the specified rating.
- Reinstall the control box cover (three screws), middle panel (two screws), glossy black panel and top slate panel.
- Restore power at the external line switch and verify operation.
Applies to: SVF 1500-3000 Series 1 boiler
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF Series 1 boiler manual, p. 100. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.