Float type low water cutoff: clean and test

CGa Series 4CGi Series 5EG Series 7PEG Series 7LGB Series 2 & 3

What is going on

Periodic cleaning and function test of a float type low water cutoff. Boiler pressure and temperature must be low first.

Check in this order

  1. Make sure the boiler is cool and pressure is low to avoid burns.
  2. Open the blowdown valve at the bottom control and drain into a bucket to flush sediment from the float chamber.
  3. Turn the operating control to call for heat before the water gets hot.
  4. Drain water until the level drops to the bottom of the gauge glass; the boiler should shut off after the level drops a few inches.
  5. Refill to the correct waterline; the boiler should start again.

Applies to: Float type low water cutoff

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Gas-Fired Boilers User Manual 550-100-226/0425, p. 20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.