Weil-McLain · Boiler troubleshooting
Float type low water cutoff: clean and test
What is going on
Periodic cleaning and function test of a float type low water cutoff. Boiler pressure and temperature must be low first.
Check in this order
- Make sure the boiler is cool and pressure is low to avoid burns.
- Open the blowdown valve at the bottom control and drain into a bucket to flush sediment from the float chamber.
- Turn the operating control to call for heat before the water gets hot.
- Drain water until the level drops to the bottom of the gauge glass; the boiler should shut off after the level drops a few inches.
- Refill to the correct waterline; the boiler should start again.
Applies to: Float type low water cutoff
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Gas-Fired Boilers User Manual 550-100-226/0425, p. 20. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.