What is going on

The CU3A is a direct vent appliance and can be sealed-combustion in any room size or ventilation type. It can go in living areas, unventilated utility rooms, closets, alcoves and attics with a direct flue outlet, with no clearance needed from combustibles. Follow local and national codes. Concentric PP(s) direct vent systems are certified with the boiler. Single-wall venting (AL29-4C, PP(s) or CPVC, listed for category IV) is also allowed. Max flue gas temperature is 230°F (110°C), so no flue temperature protection is needed. Use the Vitocrossal 300 CU3A venting instructions for details.

Check in this order

  1. Install as a sealed-combustion direct vent unless using an approved single-wall system.
  2. Use only a certified concentric or approved single-wall venting system.
  3. Confirm flue pipe rating is at least 230°F (110°C).

Applies to: Vitocrossal 300 CU3A

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CU3A application guide, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.