Condensate neutralizer maintenance

NCB700

What is going on

Check neutralizer media and outlet pH regularly. Test once a year with pH strips or an electronic meter. Replace the media when pH falls below the local water authority minimum, or below 6.0 if no minimum is specified.

Likely causes

  • Neutralizing media used up by condensate flow
  • Condensate trap debris

Check in this order

  1. Periodically check the media level in the neutralizer.
  2. Test the outlet pH at least once a year.
  3. Replace the neutralizing media when pH drops below the local minimum, or below 6.0 if none is set.
  4. During the first year, check the neutralizer every few months for depletion.
  5. Once a year, drain the condensate trap, clean out debris and refill with fresh water through the access port.
  6. Order replacement media from your local Navien distributor.

Applies to: NCB700 condensate neutralizer

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 27-28. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.