Viessmann · Boiler troubleshooting
Check boiler room air supply and barometric draft regulator
What is going on
Confirm combustion air and draft control work during operation.
Likely causes
- Fresh air intake blocked or partly covered
- Barometric draft regulator stuck
Check in this order
- Make sure the boiler room fresh air intake is open and never blocked or partly covered.
- With the burner running, confirm the barometric draft regulator in the vent system moves freely.
Applies to: VR1 40 to 63, 161 to 245
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100 installation and service manual, p. 50. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.