Viessmann · Boiler troubleshooting
Gas piping installation and leak test
What is going on
Size the gas pipe from the run length, number of fittings, gas type and total input of all gas appliances, following CAN/CSA B149.1 and .2 or NFPA 54 / ANSI Z223.1. Keep piping clear of serviceable components. Test pressure that is too high can damage the burner and gas fittings. Do not vent gas piping above the combustion chamber.
Check in this order
- Before connecting the boiler, install a ground joint union, a capped drip leg and a manual shut-off valve listed by a recognized testing agency.
- Connect the NG line to the NG shut-off valve and the LPG line to the LPG shut-off valve.
- Leak test the piping with an approved method.
- Purge the gas line safely with an approved purge burner.
- Install a gas filter if the gas pipe may contain dirt.
- Tag the shut-off valves and explain them to the owner.
- Open the manual gas valve, leak test all connections with a certified leak detector, close the valve, and repair any leaks.
- Repeat the valve leak test for the other fuel.
- Install the drip pocket per CAN/CSA B149.1 or NFPA 54.
Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocrossal 300 CA3B Dual Fuel installation manual, p. 42-43. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.