Initial system fill and freeze protection

Vitorond 200 VD2

What is going on

Fill and purge the system with the spring-loaded flow check valves open, then close them. Antifreeze use requires care.

Likely causes

  • Hard or high mineral content feed water
  • Freezing risk in the installed area

Check in this order

  1. Manually open the spring-loaded flow check valves before filling.
  2. Fill the system and purge all air.
  3. Once the system is full and purged, close the flow check valves again so they are in flow-check operation.
  4. Consider water treatment where feed water has high mineral content or hardness.
  5. If antifreeze is used, use only a product made for hot water heating systems and follow its manufacturer's specifications.
  6. A 40% antifreeze mix protects to -10°F (-23°C).
  7. Do not use automotive silicate-based antifreeze.
  8. Check the total system often when filled with antifreeze, and check whether a backflow preventer is needed on the automatic feed.

Applies to: VD2-320 to VD2-1080

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2 installation manual, p. 36. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.