Viessmann · Boiler troubleshooting
Initial system fill and freeze protection
What is going on
Fill and purge the system with the spring-loaded flow check valves open, then close them. Antifreeze use requires care.
Likely causes
- Hard or high mineral content feed water
- Freezing risk in the installed area
Check in this order
- Manually open the spring-loaded flow check valves before filling.
- Fill the system and purge all air.
- Once the system is full and purged, close the flow check valves again so they are in flow-check operation.
- Consider water treatment where feed water has high mineral content or hardness.
- If antifreeze is used, use only a product made for hot water heating systems and follow its manufacturer's specifications.
- A 40% antifreeze mix protects to -10°F (-23°C).
- Do not use automotive silicate-based antifreeze.
- Check the total system often when filled with antifreeze, and check whether a backflow preventer is needed on the automatic feed.
Applies to: VD2-320 to VD2-1080
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2 installation manual, p. 36. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.