Weil-McLain · Boiler troubleshooting
ECO Tec S2 will not light after gas conversion
What is going on
Coarse gas valve settings get the boiler to light. Final set-up must be done with a combustion analyzer in Manual Test Mode.
Likely causes
- Throttle or offset screw not set to the coarse position
- Fuel type in the control does not match the gas
- Max or min rate set wrong
Check in this order
- Gas qualified tech only. Use a calibrated flue gas analyzer.
- Make sure Fuel Type in Boiler Settings matches the gas (propane or natural gas).
- Propane coarse settings (throttle turns CCW from bottomed out): 80/110 = 6-3/4, 150 = 10-3/4, 199 = 13. Offset from the factory NG mark: 80/110 = 1/8 turn CCW, 150 and 199 = 0.
- Natural gas coarse throttle turns 80/110 = 9-1/8; 150 and 199 per Figure 22 (text reads 12 and 14-1/2, check the page).
- Bottom out the throttle screw gently. Never bottom out the offset screw.
- Still will not light turn the throttle CCW 1/4 turn more and try again, up to one full extra turn. Still no light, or O2 under 1.0%: call Weil-McLain tech support.
- Before firing, Max Rate should be 96 to 100% and Min Rate 10%.
- Set high fire with the throttle screw, then low fire with the offset screw, to the CO2/CO ranges on p.125. Do not let it modulate until combustion is set.
Applies to: ECO Tec 80/110/150/199 Series 2 heating only
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Gas conversions p.17-18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.