Viessmann · Boiler troubleshooting

Clean combustion chamber and heat exchanger surface

Vitodens 200-W

What is going on

Remove debris and sediment from the combustion chamber and stainless steel heat exchanger. Discoloration of the heat exchanger is normal and does not affect function or life.

Likely causes

  • Sediment buildup on heat exchanger
  • Debris in combustion chamber
  • Debris plugging heat exchanger coil gaps

Check in this order

  1. Remove the burner assembly and reinstall it when service is complete, per the burner instructions on page 23.
  2. Vacuum loose debris out of the combustion chamber.
  3. Rinse embedded sediment off the stainless steel heat exchanger with water or an approved cleaning agent. Follow the agent's safety and application instructions and wear protective equipment.
  4. Do not use a metal wire brush or mechanically driven brush. Keep the refractory dry.
  5. If heat exchanger coil gaps are plugged, remove debris with the Viessmann tool made for this purpose, without scratching the surface.
  6. Flush the combustion chamber with water until it runs clear through the condensate trap.
  7. Clean out debris from the condensate trap and reinstall it.

Applies to: Vitodens 200-W B2HA 80 to 100 and 285 to 352

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Service Instructions, p. 25. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.