Viessmann · Boiler troubleshooting
Check the condensate drain and clean the siphon
What is going on
If condensate cannot drain freely it builds up in the bottom of the boiler and the burner shuts down with a fault message.
Likely causes
- Condensate not draining freely from the siphon
- Debris in the siphon trap
- Condensate pipe incorrectly connected to the siphon or heat exchanger
Check in this order
- Check that condensate drains freely in the siphon.
- Pull off retaining clip A.
- Pull filler pipe B upwards.
- Pull trap C downwards.
- Disconnect the condensate hose from trap C.
- Clean the siphon.
- Fill the siphon with water and reassemble.
- Check that the condensate pipe is connected correctly to the siphon and heat exchanger.
Applies to: Condensate drain and siphon
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 222-F B2TB 19, 35, 68, 125 Service Instructions, p. 25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.