Weil-McLain · Boiler troubleshooting
Freeze protection with antifreeze
What is going on
Use only antifreeze made for hydronic systems. Inhibited propylene glycol is recommended.
Check in this order
- Do not use ethylene glycol, automotive antifreeze or undiluted antifreeze.
- Work out the antifreeze quantity from the total system water content, including the expansion tank. Boiler water content is listed on page 89.
- Follow the antifreeze manufacturer's instructions.
- A 50% propylene glycol and water solution gives maximum protection to about -30°F.
- Check local codes for a backflow preventer or a full disconnect from the city water supply.
- If the system has automatic fill, install a water meter to track makeup water. Glycol leaks out before water does, so a drop in glycol level can be missed without it, and added water dilutes the antifreeze.
Applies to: All EG / PEG Series 7 boilers with glycol
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG / PEG Series 7 Boiler Manual, p. 56. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.