Viessmann · Boiler troubleshooting

Connecting a low water cut-off (LWCO)

Vitocrossal 300 CA3B Dual Fuel

What is going on

The LWCO switching contact is wired in place of the factory jumper. Use the diagram in the LWCO device manual for interconnection details.

Check in this order

  1. Disconnect power to the control.
  2. Remove the jumper between terminals 15 (L) and 16 (L).
  3. Wire the LWCO switching contact to terminals 15 (L) and 16 (L).
  4. Power the LWCO device from an available L, N, G terminal at 12, 13 or 14.

Applies to: Low water cut-off device

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel installation instructions, p. 29. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.