Weil-McLain · Boiler troubleshooting

Steam relief valve popping

Weil-McLain SGO Series 4

What is going on

Water or steam keeps coming out of the relief valve.

Likely causes

  • Pressure limit control not working or set too high
  • Wrong relief valve or a weak valve opening early

Check in this order

  1. Turn the burner off if pressure is near 15 psi.
  2. Check the pressure control setting, its wiring and that it actually shuts the burner off. Replace it if it does not.
  3. Confirm the relief valve is rated 15 psi. If it opens below 15 psig, replace it.
  4. Test the pressure control with the burner running, move the setting below the actual steam pressure. Burner must stop. Move it back up and the burner should relight.

Applies to: SGO-3 to SGO-9 oil-fired steam boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SGO Series 4 Steam Boiler Manual 550-142-330/0825, Troubleshooting p.7; Check out procedure p.35. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.