Checking boiler, DHW tank, and flow/low-loss header temperature sensors
What is going on
Resistance check of the boiler water sensor, fixed high limit, DHW tank sensor and flow sensor for the low-loss header. Sensor type NTC 10 kΩ. The resistance curve chart is not legible in this extract.
Likely causes
- Sensor or lead faulty
Check in this order
- Boiler temperature sensor remove lead to boiler water temperature sensor and check resistance.
- DHW tank sensor pull plug from the cable harness at the control unit and check resistance.
- Supply or low-loss header sensor pull plug X3 from the control unit and check resistance across X3.4 and X3.5. Only one temperature sensor may be used.
- Compare actual values with the curve.
- Replace the sensor if severe deviation.
- Warning: the boiler temperature sensor is immersed in heating water (scald risk). Drain the boiler before replacing the sensor.
Applies to: Vitodens 200-W B2HA 45, 60
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 79. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.