Viessmann · Boiler troubleshooting

Checking boiler, DHW tank, and flow/low-loss header temperature sensors

Vitodens 200-W B2HA

What is going on

Resistance check of the boiler water sensor, fixed high limit, DHW tank sensor and flow sensor for the low-loss header. Sensor type NTC 10 kΩ. The resistance curve chart is not legible in this extract.

Likely causes

  • Sensor or lead faulty

Check in this order

  1. Boiler temperature sensor remove lead to boiler water temperature sensor and check resistance.
  2. DHW tank sensor pull plug from the cable harness at the control unit and check resistance.
  3. Supply or low-loss header sensor pull plug X3 from the control unit and check resistance across X3.4 and X3.5. Only one temperature sensor may be used.
  4. Compare actual values with the curve.
  5. Replace the sensor if severe deviation.
  6. Warning: the boiler temperature sensor is immersed in heating water (scald risk). Drain the boiler before replacing the sensor.

Applies to: Vitodens 200-W B2HA 45, 60

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 79. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.