Viessmann · Boiler troubleshooting

Open the control unit and power pump module

Vitodens 100-W WB1B

What is going on

The boiler ON/OFF switch does not disconnect power to the power/pump module. Turn off the main service switch or breaker before opening the module.

Check in this order

  1. Turn off the main service switch or breaker.
  2. Loosen the screws underneath the boiler without removing them, then remove the cover.
  3. Pull the tabs outward.
  4. Flip the control unit down.
  5. Remove the cover by releasing the tabs if necessary.
  6. Unlock the 4 spring-loaded lock screws (B) and remove the power pump module cover plate.

Applies to: Vitodens 100-W WB1B control unit and power pump module

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 100-W WB1B installation and service manual, p. 50. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.