Metal flakes in the flue passages

Weil-McLain WTGO Series 4

What is going on

Flakes of metal are found in the flueways. Either chemicals in the combustion air are attacking the boiler, or flue gas is condensing because the burner is not set right.

Likely causes

  • Combustion air contaminated by chemicals (bleach, cleaners, sprays, fabric softener, paint remover)
  • Flue gas condensing in the boiler

Check in this order

  1. Look for chemicals stored near the boiler and remove them.
  2. Check that the nozzle is the right size and that the oil pump pressure gives the correct firing rate.
  3. Set combustion with an analyzer.
  4. Clean the flueways after the cause is fixed.

Applies to: WTGO-3 to WTGO-9 oil-fired cast iron boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain WTGO Series 4 Boiler Manual 550-142-332/0225, Troubleshooting, p.7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.