Viessmann · Boiler troubleshooting

External demand

Vitodens 200-W

What is going on

External contact requests heat and can enforce a minimum boiler water temperature.

Check in this order

  1. Wire the floating contact to DE1, DE2 or DE3.
  2. Set the input to 3A:2, 3B:2 or 3C:2.
  3. Set pump response with 3F (internal pump), D7 (heating circuit pump) and 5F (DHW circulation pump).
  4. Set the minimum set boiler water temperature with 9B.

Applies to: Vitodens 200-W B2HA 80 to 100

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA Service Instructions, p. 90. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.